Hall-Effect Current Sensor

HC-MSL  Large current range / Bolt on type RoHS compliant

HC-MSL

Dimensional outline drawing

Characteristics charts

Features

  • Rated current: 300A–3000A
  • Screw type control terminals also available

Applications

Inverters, Power supply equipment, Uninterruptible power supply (UPS), NC machine tools, Welders

Detailed data

Electrical characteristics Ta=25℃

Type HC-MSL
300V4B15
HC-MSL
600V4B15
HC-MSL
E10V4B15
HC-MSL
E15V4B15
HC-MSL
E30V4B15
Rated current [If] ±300A ±600A ±1000A ±1500A ±3000A
Saturation current [Is] ±900A ±1200A ±2400A ±2400A ±5000A
Linearity limits 0~±900A 0~±1000A 0~±2100A 0~±2100A 0~±4500A
Rated output [Vh] ±4V±1% ±4V±2%
Residual output [V0] Within ±30mV
Output linearity Within ±1%
Response time Within 10μs (at di/dt=100A/μs)
Response performance Within 10%
Hysteresis voltage range Within 30mV
Output Temp. Coef. Within ±0.1%/℃
Residual output Temp. Coef. Within ±1mV/℃
Control power supply ±15V±5%
Consumption current Within 30mA Within 50mA
Operating Temp. -10℃~+80℃
Storage Temp. -15℃~+85℃
Dielectric withstand voltage 2500V AC 50/60Hz 1minute
Insulation resistance Not less than 500MΩ 500V DC
Note1)
The indicated rated output is the one when no load is applied.
Note2)
The indicated residual voltage is the one after the core hysteresis is removed.

Consultations and Inquiries about Our Products

Current sensor user's guide

When using our current sensors, please read the following “Handling Precautions,” “Main Characteristics,” and “Product Labeling” and use them within the specified limits.

Click here for FAQs about current sensors

Contact us by e-mail or phone

+81-865-66-4877

PageTop